VESSELS UNDER PRESSURE REGULATIONS
Contents
1. Definitions
2. Scope of application
3. Design, construction and manufacture
4. Manufacturer's data plate
5. Registration of a boiler
6. Appurtenances
7. Automatic controls and indicators
8. Access
9. Door interlocks
10. Portable gas containers
11. Hand-held fire extinguishers
12. Gas fuel use, equipment and systems
13. Inspection and test
14. Record keeping
15. Maintenance
16. Modification and repair
17. Approved inspection authorities
18. Offences and penalties
19. Repeal of regulations and annexures
20. Short titleAnnexure 1
Incorporation of health and safety standards - GN R1625 of 1996
Exemption - GN R1626 of 1996
Exemption - GN R1071 of 1997
VESSELS UNDER PRESSURE REGULATIONS
[Note-These regulations were published under Government Notice R1591 in Government Gazette 17468 of 4 October 1996 and amended by: GN R1 of 8 January 1999.]
Occupational Health and Safety Act, 1993
________________________________________________________________
No. R1591 4 October 1996
The Minister of Labour has under section 43 of the Occupational Health and Safety Act, 1993 (Act No. 85 of 1993), after consultation with the Advisory Council for Occupational Health and Safety, made the regulations in the Schedule.
Schedule
________________________________________________________________
1. In these regulations "the Act" means the Occupational Health and Safety Act, 1993 (Act No. 85 of 1993), and any expression to which a meaning has been assigned in the Act shall have the meaning so assigned and, unless the context indicates otherwise-
"boiler" means any apparatus to convert continuously any liquid into steam, vapour or gas at a pressure higher than that due to the atmosphere and where the heat is derived from a source other than steam or the ambient temperature of the atmosphere, and includes any super heater or economiser which is an integral part of a boiler or is separately fired therefrom, but does not include such an apparatus, superheater or economiser in which the product of the design pressure in pascal and the volume in cubic metres is less than the figure 15 000;
"design pressure" means the pressure used in the design formulae to determine the dimensions of the component parts of a vessel under pressure;
"flammable liquid" means any liquid which produces a vapour that forms an explosive mixture with air, and includes any liquid with a closed-cup flash-point of less than 55C
"gas fuel" means any liquefied petroleum gas, coal produced gas or natural gas;
" gas fuel system" means an assembly of tubes, pipes or similar ducts, fitting and valves for the process and conveyance of a gas fuel, excluding a boiler, pressure vessel or portable gas container connected to the system;
"gauge pressure" means the pressure in excess of that due to the atmospheric pressure;
"hand-held fire extinguisher" means a rechargeable container which has a fire extinguishing substance that is expelled by the action of internal pressure for the purpose of extinguishing a fire;
"hazardous chemical substance" means a substance defined as such in regulation 1 of the Regulations for Hazardous Chemical Substances published under Government Notice No. R. 1179 of 25 August 1995;
"maximum permissible operating pressure" means the maximum gauge pressure at which a vessel under pressure may be operated;
"modification" means any change from the original design criterion of the vessel under pressure and "modify" has a corresponding meaning;
"portable gas container" means any cylinder or other vessel of which the water capacity by volume is at least 0,5 litres, but does not exceed 1200 litres and which is intended for the storage and conveyance of compressed, liquefied or dissolved gases;
"pressure vessel" means any vessel of which the interior or jacket is under pressure or in which a cushion of gas or vapour can form above the liquid at a pressure in excess of that of the atmosphere, including a diving bell, but does not include
(a) a boiler;
(b) a vessel in which the pressure is exerted by a liquid the temperature of which does not exceed the boiling point of the liquid at atmospheric pressure and in which a cushion of gas or vapour cannot form above the liquid;
(c) the working cylinders or chambers of a steam, heat or air engine;
(d ) a vessel under pressure which forms an integral operating part of a motor vehicle or locomotive running on railway lines;
(e) a portable gas container;
(f ) a pressurised system;
(g) a vessel of which the product of the design pressure in pascal and the capacity in cubic metres is less than the figure 15 000;
(h) a vessel of which the design pressure is less than 40 000 pascal gauge pressure;
(i) a vessel with a nominal internal diameter of less than 150 mm; or
(j ) a handheld fire extinguisher;
"pressurised system" means an assembly of vessels under pressure and includes connections by pipes or similar ducts, fittings and valves which operate under gauge pressure equal to or greater than 40 000 pascal for the process and conveyance of a flammable liquid, hazardous chemical substance, saturated steam or superheated steam;
"provincial director" means the provincial director as contemplated in regulation 1 of the General Administrative Regulations published under Government Notice No. R. 1449 of 6 September 1996, as amended;
"repair" means a repair to any part subjected to pressure from a vessel under pressure that requires the application of heat or welding, or the replacement of more than 20% of expanded tubes in a boiler or pressure vessel at any one time and "repairing" has a corresponding meaning;
"SABS 1475" means the Standard Specification for the Production of Reconditioned Firefighting Equipment, SABS 1475, Part 1: Portable Fire Extinguishers, published by the South African Bureau of Standards (SABS);
"SABS 0227" means the Code of Practice for The Evaluation of the Technical Competence of Inspection Authorities for the Certification of Vessels under Pressure, SABS 0227, published by the South African Bureau of Standards (SABS); and
"vessel under pressure" means a vessel which operates under pressure and includes a boiler, pressure vessel, pressurised system or portable gas container.
2. These regulations shall apply to all users of vessels under pressure: Provided that regulation 3 shall not apply to a boiler, pressure vessel or portable gas container in use prior to 23 October 1992, and which was designed, constructed and manufactured in accordance with regulations in force at that time.
Design, construction and manufacture
3. (1) Subject to the provisions of subregulation (2), no user shall use, require or permit the use of any vessel under pressure unless
(a) it has been designed and constructed in accordance with a health and safety standard incorporated into these regulations in terms of section 44 of the Act;
(b) it has been manufactured under the supervision of an approved inspection authority as contemplated in regulation 1 7 (1) (a) or any other inspection authority outside the Republic recognized by the chief inspector; and
(c) the user is in possession of a certificate of manufacture issued by the manufacturer in which it is certified that the boiler, pressure vessel or portable gas container has been designed, constructed and tested in every respect in accordance with the standard contemplated in subregulation (1) (a): Provided that such a certificate shall be countersigned by the approved inspection authority as evidence that the design of such a boiler, pressure vessel or portable gas container has been verified and that it has been constructed and tested under their supervision in accordance with the said standard.
(2) The certificate required by subregulation (1) (c) in the case of a pressure vessel or portable gas container may refer to more than one pressure vessel or portable gas container: Provided that each pressure vessel or portable gas container has the same design pressure and dimensions, and that the product of the design pressure in pascal and the volume in cubic metres of that vessel does not exceed the figure 500 000.
4. (1) Every user of a boiler or pressure vessel shall cause a manufacturer's plate with the following minimum particulars to be securely fixed in a conspicuous place to the shell of every such boiler or pressure vessel:
(a) Name of manufacturer;
(b) country or origin;
(c) year of manufacture;
(d ) manufacturer's serial number;
(e) name, number and date of the standard of design;
(f ) design gauge pressure in pascal;
(g) maximum permissible operating pressure in pascal;
(h) operating temperature;
(i) capacity in cubic metres; and
(j) mark of an approved inspection authority.
(2) No person shall remove such a manufacturer's plate or wilfully damage or alter the particulars stamped thereon, except as provided in regulation 16 (4).
5. (1) No user shall use a boiler unless the user is in possession of a certificate of registration issued in terms of subregulation (3) for that boiler: Provided that a boiler registered with the Department prior to 23 October 1992 shall be deemed to be registered in terms of this regulation: Provided further that a boiler registered after 23 October 1992 shall on change of ownership be required to be reregistered.
(2) Any user who wishes to use a boiler shall apply to the provincial director for registration of that boiler on a form similar to Annexure 1, prior to such use: Provided that this subregulation shall not apply in respect of the reerection of a boiler on the same premises.
(3) On receipt of an application contemplated in subregulation (2), the provincial director shall forward such an application to an inspector who may issue a certificate of registration in the form of Part C of Annexure 1 in respect of that boiler, subject to such conditions as may be specified on the certificate.
(4) Any user of a boiler for which a certificate of registration has been issued in terms of subregulation (3) or a certificate issued by the Department prior to 23 October 1992, shall cause the certificate of registration to be made available for inspection by an inspector or on request by an approved inspection authority or a competent person.
(5) The user shall within seven days after the discovery that the certificate of registration has been lost, defaced, destroyed or any such an occurrence, apply to the provincial director in the form similar to Part A of Annexure 1 for the issue of a duplicate certificate, and affix R100 in the form of uncancelled revenue stamps to such an application. On receipt of such application the provincial director shall submit the application to an inspector who shall issue the duplicate certificate on satisfaction that the original certificate was lost, defaced or destroyed.
(6) An inspector may at any time amend, suspend or cancel a certificate of registration issued in terms of subregulation (3).
(7) Any user of a boiler shall forthwith notify the provincial director in writing when
(a) such boiler is no longer in use;
(b) the right of control over the use of the boiler is transferred by the user to any other user, in which case the user shall also furnish the provincial director with the name and address of such new user; or
(c) the user moves the boiler to premises other than the premises reflected on its certificate of registration.
(8) A certificate of registration issued in terms of subregulation (3) shall lapse
(a) when it is cancelled by an inspector;
(b) upon the transfer of the right of control over the use of the boiler to another user; or
(c) when a boiler is removed from the premises reflected on its certificate of registration.
6. (1) No user shall require or permit a vessel under pressure to be used unless it is provided with all the appurtenances as required by the health and safety standard used in the design, construction and manufacture of such a vessel under pressure: Provided that alternative appurtenances other than those required by the standard shall only be fitted with the written approval of an approved inspection authority.
(2) In the absence of such a requirement in the health and safety standard used in the design, construction and manufacture of such a vessel under pressure, appurtenances shall be provided by the user as required by the approved inspection authority and those appurtenances shall be so selected, arranged and installed as to be safe for the particular purpose for which the vessel under pressure is to be used.
(3) Every user of a boiler or pressure vessel shall ensure that the boiler or pressure vessel in use is fitted with at least one pressure gauge and the maximum permissible operating pressure shall be clearly marked with a red line on the dial of the pressure gauge.
(4) Every user of a boiler or pressure vessel shall ensure that the boiler or pressure vessel in use is fitted with at least one safety valve and such safety valve shall be kept locked, sealed or otherwise rendered inaccessible to any unauthorised person: Provided that the number and capacity of the safety valve shall be to the requirements of the design standard for the boiler or pressure vessel or as required under subregulation (2).
Automatic controls and indicators
7. Every user shall ensure that the automatic controls and indicators of a boiler, pressure vessel or pressurised system are arranged, installed, maintained and operated in accordance with the provisions of the health and safety standard used in the design and manufacture of the boiler, pressure vessel or pressurised system: Provided that in the absence of such provisions, where automatic controls and indicators are installed, they shall be selected, arranged and installed subject to the written approval of an approved inspection authority.
8. The user shall cause every boiler, pressure vessel or pressurised system to be erected in such a manner that access to and exit from any chamber, flue, manhole, inspection opening, control or appurtenance is safe and unobstructed.
9. Any user of a pressure vessel or pressurised system shall cause such vessel or system which for operational purposes is equipped with a removable or hinged door to be provided with an interlock or other effective means for preventing
(a) a rise of pressure inside the pressure vessel or pressurised system before the removable or hinged door is in the fully closed and locked position; and
(b) the release of the removable or hinged door from the locked and closed position before the pressure inside the pressure vessel or pressurised system has been reduced to atmospheric pressure.
10. No user shall use or require or permit a portable gas container to be used, and no user shall fill, place in service, handle, modify, repair, inspect or test any portable gas container, other than in compliance with the standards incorporated into these regulations in terms of section 44 of the Act.
11. (1) No user shall use, require or permit the use of a handheld fire extinguisher unless designed, constructed, filled, recharged, reconditioned, modified, repaired, inspected or tested in accordance with a safety standard incorporated into these regulations in terms of section 44 of the Act.
(2) No person shall fill, recharge, recondition, modify, repair, inspect or test any handheld fire extinguisher unless a holder of a permit issued by the South African Bureau of Standards in terms of SABS 1475.
Gas fuel use, equipment and systems
12. (1) No person shall handle, store or distribute a gas fuel in any manner, including the filling of a container, other than in accordance with a health and safety standard incorporated into these regulations under section 44 of the Act.
(2) No person shall install a fixed appliance, equipment or system for gas fuel in any manner other than in accordance with a safety standard incorporated into these regulations under section 44 of the Act.
(3) No person shall install a fixed appliance, equipment or system for gas fuel as contemplated in subregulation (2), unless such person is a holder of a certificate of registration issued by an organisation approved by the chief inspector: Provided that subregulations (2) and (3) shall come into effect on 1 August 1997.
13. (1) Any user of a boiler or pressure vessel shall cause, where reasonably practicable, such a boiler or pressure vessel, including the appurtenances and automatic controls and indicators, to be subjected to an internal and external inspection and a hydraulic pressure test to 1,25 times the maximum permissible operating pressure as the case may be-
(a) by an approved inspection authority before commissioning after installation, re-erection or repairs; and
(b) by a person appointed in writing by the user and who is competent to do such inspections and tests by virtue of their training, knowledge and experience in the operation, maintenance, inspection and testing of a boiler or pressure vessel within 36 months from the date of the previous internal and external inspection and hydraulic pressure test: Provided that where a pressure vessel is not subjected to corrosion, the user may dispense with the internal inspection and hydraulic pressure test subject to the written approval of an approved inspection authority: Provided further that an inspector may require a specific boiler or pressure vessel to be inspected or tested more frequently or permit a specific boiler or pressure vessel to be inspected or tested less frequently:
Provided that no person shall perform internal and external inspections and hydraulic pressure tests contemplated in subregulation (1) (b) unless he or she is a holder of a certificate of registration issued by an organisation approved by the chief inspector: Provided further that this proviso shall come into effect 12 months after the publication of this regulation.
[Reg. 13 amended by GN R1 of 1999.]
(2) Any user of a pressurised system shall, where reasonably practicable, cause such pressurised system to be subjected to an inspection and hydraulic test by an approved inspection authority before commissioning, after installation or reerection.
(3) Any user of a gas fuel system shall, where reasonably practicable, cause the system to be subjected to an inspection and hydraulic test by a registered person in terms of regulation 12 (3), before commissioning, after installation or reerection.
(4) Where it is impracticable to use a liquid for the hydraulic pressure test contemplated in subregulation (1), (2) or (3), the test may, subject to the prior written approval of an approved inspection authority, be carried out with a nonflammable gas to a pressure of 1,1 times the maximum permissible operating pressure: Provided that, where reasonably practicable, the test must be preceded by an internal inspection and on such further conditions and precautionary measures as determined by the approved inspection authority.
(5) Where an inspection or test carried out in terms of subregulation (1), (2), (3) or (4) reveals any weakness or defect whereby the safety of persons may be endangered, the weakness or defect shall be reported immediately to the user by the person carrying out the inspection or test and the user shall forthwith cease the use of the boiler, pressure vessel, pressurised system or gas fuel system until such weakness or defect has been rectified to the satisfaction of the approved inspection authority concerned or the person who carried out the inspection, as the case may be.
14. Any user of a vessel under pressure shall keep on the premises a record, which shall be open for inspection by an inspector and in which the results of all inspections, tests, modifications and repairs shall be recorded, dated and signed by the competent person.
15. (1) No user shall use, cause or permit a vessel under pressure or gas fuel system, including all automatic controls, indicators and appurtenances, to be used unless it is at all times maintained in a safe working condition and the efficiency thereof is proved by regular testing.
(2) No user shall use, cause or permit a vessel under pressure to be used unless it is kept clean and free from any-
(a) carbonised oil or other flammable material which may ignite;
(b) substance which may cause corrosion; or
(c) substance which is liable to chemical reaction which may cause an uncontrolled rise in pressure.
16. (1) Any person who intends to modify or repair a boiler, pressure vessel or portable gas container shall cause such modification or repair to be carried out under the supervision of an approved inspection authority, as contemplated in regulation 17 (1) (b).
(2) Any modifier or repairer carrying out any modification or repair, as contemplated in subregulation (1), shall issue a certificate in which the extent of the modification or repair is described and certify that such work is in accordance with a health and safety standard incorporated into these regulations: Provided that such certificate shall be countersigned by the approved inspection authority as evidence that the design of such modification or repair has been verified and that it has been modified or repaired and tested under their supervision in accordance with the said health and safety standard.
(3) Whenever it appears from an inspection or test that a boiler or pressure vessel cannot be used with safety at its maximum permissible operating pressure and the user declines to have the necessary renewals or repairs effected the user shall ensure that-
(a) an approved inspection authority fixes a new reduced maximum permissible operating pressure; and
(b) that the boiler or pressure vessel is not used at a pressure higher than the new reduced pressure.
(4) The user shall cause the reduced maximum permissible operating pressure as calculated under subregulation (3) (a) to be marked on the manufacturer's plate on which the approved inspection authority shall also place its mark and no user shall thereafter require or permit such a boiler or pressure vessel to be used at a pressure higher than such a reduced pressure: Provided that in the case of a boiler the registration certificate together with a copy of the approved inspection authority's report shall be forwarded to the provincial director for correction.
Approved inspection authorities
17. (1) The chief inspector may approve any organisation that has been accredited in terms of-
(a) SABS 0227 Part 1 to perform the functions regarding the certification of new vessels under pressure, inspections and testing; or
(b) SABS 0227 Part 2 to perform the functions regarding the certification of modified or repaired vessels under pressure, inspections and testing, as an approved inspection authority.
(2) Application for approval for an organisation as contemplated in subregulation (1), must be accompanied by a valid certificate issued by the South African Bureau of Standards in terms of SABS 0227 Part 1 and or Part 2.
(3) The chief inspector may at any time withdraw any approval of an approved inspection authority, subject to the provisions of section 35 of the Act.
18. Any person who contravenes or fails to comply with the provisions of regulation 3 (1), 4, 5 (1), 5 (2), 5 (4), 5 (5), 5 (7), 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 or 16 shall be guilty of an offence and is on conviction liable to a fine or to imprisonment for a period not exceeding twelve months and, in the case of a continuous offence, to an additional fine of R200 for each day on which the offence continues or additional imprisonment of one day for each day on which the offence continues: Provided that the period of such additional imprisonment does not exceed 90 days.
Repeal of regulations and annexures
19. The following regulations, notices and annexures are hereby repealed:
(a) Notice of the incorporation of the safety standard published under Government Notice No. R. 2357, dated 25 November 1988;
(b) Vessels under Pressure Regulations, 1992, Annexure 1 and the schedule published under Government Notice No. R. 2919, dated 23 October 1992; and
(c) Correction notice published under Government Notice No. R. 78 dated 22 January 1993.
20. These regulations shall be called the Vessels Under Pressure Regulations, 1996.
__________
Annexure 1
_____________________________________________________________________________
OCCUPATIONAL HEALTH AND SAFETY ACT, 1993
[Regulation 5 (2) of the Vessels under Pressure Regulations]
REGISTRATION OF A BOILER
A. APPLICATION FOR REGISTRATION OF A BOILER/DUPLICATE CERTIFICATE
| To: Provincial Director | From: (Postal address) | ||
| Department of Labour | ........................... | ||
| ............................... | ........................... | ||
| ............................... | ........................... | ||
| ............................... | ........................... | ||
| Tel. ............................. | |||
| Fax. ............................ | |||
| I (user) (legal persona) hereby apply for registration/duplicate registration certificate of a boiler, particulars of which are reflected in Part B below. | |||
| ................................ | ........................... | ||
Signature of applicant |
Date |
||
| ................................ | ........................... | ||
Name of Applicant (In Block Letters) |
Designation of applicant |
||
B. PARTICULARS OF BOILER
1. Physical address of installation ......................................................................
2. Type of boiler ..............................................................................................
3. Name of manufacturer .................................................................................
4. Country of origin ..........................................................................................
5. Year of manufacture ....................................................................................
6. Manufacturer's serial number .........................................................................
7. Name, number and date of the standard of design ..........................................
8. Design gauge pressure in pascal ......................................................................
9. Maximum permissible operating pressure in pascal ...........................................
10. Operating temperature ...................................................................................
11. Source of energy (oil, coal, gas, electricity or nuclear) .....................................
12. Steaming capacity of boiler kg of steam per hour from and at 100 °c .........
13. Name of approved inspection authority (during manufacture) ...........................
14. Copy of manufacturer's certificate shall be attached .........................................
15. Copy of approved inspection authority's commissioning report shall be attached ..............
________________________________
FOR OFFICIAL USE ONLY
_________________________________
C. BOILER REGISTRATION CERTIFICATE
The boiler of which the particulars appear above in Part B has this day ................. been registered with the official number .......................................... . Permission is hereby granted to use the boiler at a maximum permissible operating pressure of .......................................kPa.
OFFICIAL STAMP |
.....................................
SIGNATURE OF INSPECTOR
_____________________________________________________________________________
ISSUE OF DUPLICATE BOILER REGISTRATION CERTIFICATE
REVENUE STAMPS FOR DUPLICATE CERTIFICATE |
Date .....................
...........................................SIGNATURE OF INSPECTOR
Consult regulation 5 (5) for fee payable for a duplicate boiler registration certificate.
__________
Occupational Health and Safety Act,
1993
_________________________________________________________________
Incorporation
of health and safety standards:
Vessels under pressure regulations
No. R. 1625 4 October 1996
Under section 44 of the Occupational Health and Safety Act, 1993 (Act No. 85 of 1993), I, Tito Titus Mboweni, Minister of Labour, after consultation with the Advisory Council for Occupational Health and Safety, hereby incorporate in the Vessels under Pressure Regulations, 1996, the health and safety standards specified in the Schedule.
T.T. Mboweni
Minister of Labour
________________
Schedule
________________________________________________________________
1. Regulation 3 (1) (a).
AUSTRALIA
Australian Standards, standard specifications
AS 1200
Boilers and pressure vessels
AS 1210
Unfired pressure vessels - Advanced design and construction
AS 1228
Boilers: water tube type
AS 1777
Aluminium cylinders for compressed gases - seamless 0.1 kg to 130 kg.
AS 1797
Boilers: Fire tube, shell and miscellaneous
AS 2470
Steel cylinders for compressed gases welded 11 kg to 150 kg.
AS 2527
Cylinders for dissolved acetylene
AS 2873
Carbonmanganese steel cylinders for compressed gases, seamless: 0.1 kg to 500 kg.
AS 2874
High tensile Carbonmanganese steel cylinders for compressed gases, seamless: 0.1 kg to
500 kg.
AS 2875
Alloy steel cylinders for compressed gases, seamless: 0.1 kg to 500 kg.
AS 2971
Serially produced pressure vessels
AS 3577
Steel cylinders for compressed gases, welded: 150 kg to 500 kg.
AS B10
High carbon steel cylinders for the storage and transport of permanent gases.
AS B11
High carbon steel cylinders for the storage and transport of high pressure liquefiable
gases.
AS B12
Low carbon steel cylinders for the storage and transport of medium pressure liquefiable
gases.
AS Bl l l
Manganese steel cylinders for the storage
and transport of high pressure liquefiable gases.
AS B113
High tensile carbon-manganese steel cylinder for the storage and transport of permanent
gases and high pressure liquefiable gases
AS B114
Alloy steel cylinders for the storage and transport of permanent gases and high pressure
liquefiable gases.
AS B239
Welded steel cylinders for compressed gases of capacity over 10 litres up to and including
130 litres.
CANADA
Canadian Transport Commission Regulations.
TC 4BA
Welded or Brazed cylinders made of
definitely prescribed steels.
TC 4BW
Welded steel cylinders made of definitely prescribed steels with electricarc welded
longitudinal seam.
FRANCE
NFE 31-001
Boilers operating with solid, liquid or
gases fuels
NFA 49-901
Gas cylinders - seamless steel cylinders
for compressed, liquefied or dissolved gases.
NC: 1969
French code for the manufacture of unfired pressure vessels:
Design rules
GERMANY
German Institute of Standards, standard specifications
DIN 2918
Stationary shell boilers of welded construction. (Other than water tube boilers.).
DIN 4661 Gas
cylinders, welded steel gas cylinders, at test pressure 30 atu.
DIN 4663
Compressed gas containers; seamless aluminium alloy cylinders, rated for 250 Bars and 300
Bar test pressure.
DIN 4664
Compressed gas containers; seamless steel gas cylinders.
DIN 4680
Steel fixed size pressure vessels for LPG; For above ground installations, dimensions and
equipment
DIN 28020
Horizontal pressure vessels of 0.63 up to 25 cubic metres capacity.
DIN 28021
Horizontal pressure vessels of 6,3 up to 100 cubic metres storage capacity.
DIN 28022
Vertical pressure vessels; vessels for intermediate storage 0,063 up to 25 cubic metres
for use in chemical process engineering.
ADMERKBLAETTER
Technical Rules for Pressure Vessels (TRB), Druckbehvo and
all sections
Technical Rules for Steam Boilers (TRD), Dampfkv and all
sections
INTERNATIONAL
International Standards Organisation, standard specifications
ISO 831
Rules for the construction of stationary boilers.
ISO 3807
Dissolved Acetylene cylinder - Basic Requirements.
ISO 4705
Refillable seamless steel gas cylinders.
ISO 4706
Refillable welded steel gas cylinders.
ISO 5730
Stationary shell boilers of welded construction. (Other than water tube boilers.)
EEC 87-404
Directive for the construction of simple pressure vessels.
EEC 84-525
Directive for the construction of seamless, steel gas cylinders.
EEC 84-526
Directive for the construction of seamless, unalloyed aluminium and aluminium alloy gas
cylinders.
EEC 84-527 Directive for the construction
of welded unalloyed steel gas cylinders.
EN 50 052
Cast Aluminium Alloy Enclosures for Gas filled High Voltage Switchgear and Control gear
EN 286-1
Simple unfired pressure vessels designed to contain air nitrogen; Part 1 Design and
manufacture of simple pressure vessels.
EN 303-PT 1
Heating Boilers - Heating boilers with forced draught burners - Terminology, general
requirements, testing and marking.
EN 303-PT2
Heating Boilers - Heating boilers with forced draught burners - Special requirements for
boilers with atomising oil burners.
Luxfer Limited, standard specification
Luxint Luxfer gas cylinder specification: For the manufacture
of aluminium cylinders.
ITALY
Higher Institute for Accident Prevention and Safety at Work {Instituto Superiore per la
Prevenzione e la Sicurezza del Lavoro} ISPESL rules
VSR Rules Collection (Raccolta VSR) concerning design
rules for pressure vessels
VSG Rules Collection (Raccolta VSG) concerning design rules for boilers.
JAPAN
Japanese Industrial Standards
JIS B8201
Construction of steel boilers for land use.
JIS B8233 Refillable welded steel gas
cylinders for liquefied petroleum gas.
JIS B8235
Refillable welded steel gas cylinders for liquefied fluoro carbon.
JIS B8240
Construction of pressure vessels for refrigeration.
JIS B8241
Seamless steel cylinders.
JIS B8243
Construction of pressure vessels.
UNITED KINGDOM
British Standards Institution, standard specifications
BS EN 2861
Simple unfired pressure vessels designed
to contain air or nitrogen - design, manufacture and testing.
BS 399 High
carbon steel cylinders for the storage and transport of permanent gases.
BS 400 Low
carbon steel cylinders for the storage and transport of permanent gases.
BS 401 Steel
cylinders for the storage and transport of liquefied gases.
BS 537
Lancashire and Cornish boilers of riveted construction.
BS 609
Horizontal multitubular boilers of riveted construction.
BS 665
Vertical cross tube boilers of riveted construction.
BS 761
Vertical multitubular boilers of riveted construction.
BS 779
Specification for cast iron boilers for central heating and indirect hot water
supply.(Rated output 44 kW and above)
BS 1113 Design and manufacture of water
tube steam generating plant.
BS 1307
Gas-fired boilers and waste heat boilers (with or without auxiliary firing).
BS 1894
Specification for the design and manufacture of electric boilers of welded construction.
BS 1971
Specification for corrugated furnaces for shell boilers.
BS 2790
Specification for design and manufacture of shell boilers of welded construction.
BS 3023
Corrugated furnaces and smoke tubes for marine boilers.
BS 4994
Specification of the Design and Construction of vessels and tanks in Reinforced Plastics
BS 5045 Specification for seamless
transportable gas containers. Parts: 1, 2 and 3.
BS 5169
Fusion welded steel air receivers.
BS 5500
Specification for unfired fusion welded pressure vessels.
BS 6061
Specification for transportable acetylene containers.
BS 7005
Specification for design and manufacture of carbon steel unfired pressure vessels for use
in vapour compression refrigeration systems.
BS 7122
Specification for welded steel tanks for road transport of liquefied gases.
Lloyds Register, standard specifications
Lloyds Rules and Regulations for the design and construction
or use of boilers, pressure vessels, pressurised systems or portable gas containers.
UNITED STATES OF AMERICA
American Society of Mechanical Engineers, standard
specifications
ASME Section I
Power Boilers
ASME Section III
Rules for the construction of nuclear
power plant components code for concrete reactor vessels and containments.
ASME Section IV
Lowpressure Heating Boilers
ASME Section VIII Unfired Pressure Vessels
(Divisions I and 2)
ASME Section X Fibreglassreinforced
plastic pressure vessels
ASME Part B31
Pressurised piping systems: Part l-Power
piping.
Part 3-Chemical plant and petroleum refinery piping.
Part 4-Liquid transportation systems for hydrocarbons, liquid petroleum gas, anhydrous
ammonia and alcohol's.
Part 5-Refrigeration piping.
Part 8-Gas transmission and distribution piping systems.
American Petroleum Institute, standard specifications
API 620
Design & construction of large, welded, low pressure storage tanks.
United States, Department of Transport Regulations: Code of
Federal Regulations, Title 49.
DOT 4BW
Welded steel cylinders made of definitely prescribed steels with electricarc welded
longitudinal seam. Including DOT 4BA
DOT 39 Non
reusable - non refillable cylinder
DOT 8 Welded steel cylinders made of
definitely prescribed steels for the transportation of acetylene.
DOT E-1-320
Welded steel cylinders made of definitely prescribed steels electricarc welded
longitudinal seam for the transportation of acetylene.
DOT 4E Welded aluminium cylinders made of
definitely prescribed aluminium.
The Association of American Railroads
Section C, Part III - Specifications for Tank Cars, M1002
Hartford Steam Boiler Inspection and Insurance Company
HSBARS-86
Standard for air receivers.
Tubular Exchange Manufacturers Association, Inc. (TEMA)
rules.
SOUTH AFRICA
South African Bureau of Standards, standard specifications
SABS 50
The design and manufacture of seamless steel cylinders for high and low pressure service.
SABS 099 The
construction of air receivers
SABS 219 The
design and manufacture of welded steel cylinders for low pressure service.
SABS 220
Dissolved acetylene cylinders.
SABS 1571
Transportable rechargeable fire extinguishers.
South African Bureau of Standards, codes of practice
SABS 019
Portable metal containers for compressed gases: Basic design criteria, use and
maintenance.
2. Regulation 10
SOUTH AFRICA
South African Bureau of Standards, codes of practice
SABS 019 Portable metal containers for compressed gases: Basic design criteria, use and maintenance.
3. Regulation 11
SOUTH AFRICA
South African Bureau of Standards, standard specification
SABS 810
Portable rechargeable fire extinguishers - Dry powder type extinguishers.
SABS 889
Portable rechargeable fire extinguishers - Water type extinguishers.
SABS 1151
Portable rechargeable fire extinguishers -Halogenated hydrocarbon type extinguishers.
SABS 1475 The
production of reconditioned firefighting equipment.
SABS 1567
Portable rechargeable fire extinguishers - CO2 type extinguishers.
SABS 1573
Portable rechargeable fire extinguishers - Foam type extinguishers.
South African Bureau of Standards, codes of practice
SABS 0105 The
classification, use and routine maintenance of firefighting appliances. Part 1: Portable
fire extinguishers
4. Regulation 12
UNITED STATES OF AMERICA
American Society of Mechanical Engineers, standard
specifications
ASME Part B31
Pressurised piping systems: Part 3-Chemical plant and petroleum refinery piping. Part
4-Liquid transportation systems for hydrocarbons, liquid petroleum gas, anhydrous ammonia
and alcohol's. Part 8-Gas transmission and distribution piping systems.
American National Standards Institute
ANSI Z223.1
National Fuel Gas Code
SOUTH AFRICA
South African Bureau of Standards, codes of practice:
SABS 087 Handling, Storage and Distribution of Liquefied Petroleum Gas in Domestic, Commercial and Industrial Installations.
Part I: Consumer Liquefied Petroleum Gas Cylinder Installations.
Part II: Installations in Mobile Units and Small NonPermanent Buildings.
Part III: Bulk Liquefied Petroleum Gas Storage and Allied Facilities at Consumer's Premises.
Part IV: Transportation of Liquefied Petroleum Gas in Bulk by Road.
Part V: Liquefied Petroleum Gas as Engine Fuel.
Part VII: Retail outlet and similar Liquefied Petroleum Gas Filling Sites for Small Containers.
Part VIII: The Fuelling of Fork Lift Trucks and Other Liquefied Petroleum Gas Operated Vehicles.
SABS 1539 Appliances operating on liquefied petroleum gas - Portable and mobile appliances - Safety aspects.
___________________
NOTICE OF EXEMPTION IN TERMS OF SECTION
40 (1) OF THE
OCCUPATIONAL HEALTH AND SAFETY ACT, 1993
Under section 40 (3) (b) of the Occupational Health and Safety Act, 1993 (Act No. 85 of 1993), I, Faiza Salie, appointed as chief inspector in terms of section 27 (1) of the said Act, and by virtue of the power delegated to me by the Minister of Labour in terms of section 42 (1) of the Act, hereby grant exemption in terms of section 40 (1) to persons presently occupied with the activities described under regulation 11 (2) of the Vessels under Pressure Regulations, 1996, published under Government Notice No. R. 1591 of 4 October 1996, from the obligation of being holders of a permit issued by the South African Bureau of Standards in terms of SABS 1475 for a period of twelve (12) months, from the date of the commencement of the said regulations: Provided that such persons submit a written application for the required permit to the South African Bureau of Standards within six (6) months from the date of this notice
F Salie
Chief Inspector
_________________
NOTICE OF EXEMPTION IN TERMS OF SECTION
40 (1) OF THE
OCCUPATIONAL HEALTH AND SAFETY ACT, 1993
Under section 40 (3) (b) of the Occupational
Health and Safety Act, 1993 (Act No. 85 of 1993), I, Faiza Salie, appointed as chief
inspector in terms of section 27 (1) of the said Act, and by virtue of the power
delegated to me by the Minister of Labour in terms of section 42 (1) of the Act,
hereby grant exemption in terms of section 40 (1) to persons who perform installation
work for the gas fuels, coal produced or natural gas, as described under regulation 12 (3)
of the Vessels under Pressure Regulations, 1996, published under Government Notice
No. R. 1591 of 4 October 1996, from the obligation of being holders of a
certificate of registration issued by an organisation approved by the chief
inspector for a period of twelve (12) months from 1 August 1997.
F SALIE
Chief Inspector